System modules

ANALOG1_IO (node number 11)
Inputs_ANALOG1 (analog input)

13

l

276

EDBCSXA064 EN 3.2

System variables

Variable

Data

type

Signal

type

Address

Display

code

Display

format

Comments

AIN1_nIn_a

integer

analog

%IW11.0

C0400

dec [%]

Analog input 1

AIN1_bError_b

BOOL

binary

%IX11.1.0

˘

˘

Only when C0034 = 1:
TRUE, if

½I½ < 2 mA

Codes

Code

Possible settings

IMPORTANT

No.

Designation

Lenze/
{Appl.}

Selection

C0026

Offset for relative analog signals
(AIN)

^ 275

^ 347

1 FCODE(offset)

0,0

−199,99

{0.01 %}

199,99 FCODE_nC26_1_a

2 FCODE(offset)

0,0

FCODE_nC26_2_a

C0027

Gain for relative analog signals
(AIN)

^ 275

^ 347

1 FCODE(gain)

100,0

−199,99

{0.01 %}

199,99 FCODE_nC27_1_a

2 FCODE(gain)

100,0

FCODE_nC27_2_a

C0034 Mst current

0

Master voltage/master current
on analog input (AIN1_nIn_a)

^ 275

0

−10 ... + 10 V

Master voltage

1

+4 ... +20 mA

Master current

2

−20 ... +20 mA

C0400 DIS: AnalogIn

Signal at the analog input
Read only

−199.99

{0.01 %}

199.99

C0598 MONIT SD5

3

Fault response − master current
monitoring at X6 < 2 mA
"MastISourceDef"

^ 275

0

TRIP

2

Warning

3

Off