Monitoring functions

Configuring monitoring functions
DC−bus voltage monitoring (OU, LU)

10

l

218

EDBCSXA064 EN 3.2

10.3.11

DC−bus voltage monitoring (OU, LU)

Fault message

Monitoring function

System variable

Possible response

TRIP

Messag

e

Warnin

g

Off

020

OU

Overvoltage

MCTRL_bOvervoltage_b

·

030

LU

Undervoltage

MCTRL_bUndervoltage_b

·

· Default setting

üSetting possible

These monitoring functions monitor the DC bus and protect the controller.

ƒ

If the DC−bus voltage at terminals +U

G

and −U

G

exceeds the upper switch−off

threshold set in C0173, an OU message is sent.

ƒ

If the DC−bus voltage at terminals +U

G

and −U

G

falls below the lower switch−off

threshold set in C0174, an LU message is sent.

The monitoring response remains active until the corresponding threshold is fallen
below/exceeded again.

)

Note!

All drive components in DC−bus connections must have the same thresholds!

Switch−off and switch−on thresholds

ƒ

The switch−off threshold defines the voltage level of the DC−bus voltage, at which
the pulse inhibit is activated.

ƒ

The switch−off and switch−on thresholds dependent on C0173 can be gathered from
the following table: