Appendix

Code table

14

l

422

EDBCSXA064 EN 3.2

IMPORTANT

Possible settings

Code

Selection

Lenze/
{Appl.}

Designation

No.

C2357

Monitoring time for XCAN
process data input objects
(AIF interface X1)
Only ECSxA: When the subcodes
1 ... 4 are set, consider the task
runtime:
C2357/1...4 = Desired monitoring
time / task runtime

^ 192

1 CE monit time

3000

1

{1 ms}

65000 XCAN1_IN monitoring time

2 CE monit time

3000

XCAN2_IN monitoring time

3 CE monit time

3000

XCAN3_IN monitoring time

4 CE monit time

3000

Bus−off

5 CE monit time

3000

AIF monitoring time (can only be
set if C2357/6 = 0)

6 CE monit time

0

Sync monitoring time (can only
be set if C2357/5 = 0)

C2359 AIF HW Set.

0

0

{1}

65535

C2364

0

Event−controlled PDO
transmission
(AIF interface X1)

0

Send PDOs when changing to
"Operational" state

1

Do not send PDOs

C2365

Enabling the second parameter
data channel and the PDO
channels
(aIF interface X1)

1

0

0

{1}

3 Enabling the second parameter

data channel

2

1

Enabling the first process data
channel

3

1

Enabling the second process data
channel

4

1

Enabling the third process data
channel

0

Deactivated

1

Activated

2

Reception activated

3

Transmission activated

C2367 Sync Rx Id

128

XCAN receive identifier of the
sync telegram(AIF interface X1)

1

{1}

2047

C2368 Sync Tx Id

128

XCAN send identifier of the sync
telegram
(AIF interface X1)

1

{1}

2047

C2369

0

XCAN Consumer Heartbeat
COB−ID
(AIF interface X1)

0

{1}

255