System modules

CAN2_IO (node number 32)

Outputs_CAN2

13

l

293

EDBCSXA064 EN 3.2

13.9.2

Outputs_CAN2

System variables

Variable

Data

type

Signal

type

Address

Display

code

Display

format

Comments

CAN2_nOutW1_a

integer

analog

%QW32.0

C0868/4

dec [%]

CAN2_nOutW2_a

%QW32.1

C0868/5

CAN2_bFDO0_b

BOOL

binary

%QX32.0.0

C0151/2

hex

Display code in hex
as double word

...

...

CAN2_bFDO15_b

%QX32.0.15

CAN2_bFDO16_b

%QX32.1.0

...

...

CAN2_bFDO31_b

%QX32.1.15

CAN2_dnOutD1_p

double

integer

position

%QD32.0

C0869/2

dec [inc]

CAN2_nOutW3_a

integer

analog

%QW32.2

C0868/6

dec [%]

CAN2_nOutW4_a

%QW32.3

C0868/7

User data

The first 4 bytes of the 8 bytes user data to be sent can be written via several variables of
different data types. According to requirements, data can therefore be transferred from
the PLC program as

ƒ

binary information (1 bit)

ƒ

status word/quasi−analog value (16 bit)

ƒ

angle information (32 bit)

Byte

Variable (1 bit)

Variable (16 bit)

Variable (32 bit)

1, 2

CAN2_bFDO0_b

...

CAN2_bFDO15_b

CAN2_nOutW1_a

CAN2_dnOutD1_p

3, 4

CAN2_bFDO16_b

...

CAN2_bFDO31_b

CAN2_nOutW2_a

5, 6

CAN2_nOutW3_a

7, 8

CAN2_nOutW4_a

)

Note!

Avoid simultaneous overwriting via different variable types to ensure data
consistency.
If you want to describe e.g. the bytes 1 and 2, either use only the variable
CAN2_dnOutD1_p, only the variable CAN2_nOutW1_a or only the variables
CAN2_bFDO0_b ... CAN2_bFDO15_b!