Electrical installation

Control terminals

5

l

74

EDBCSXA064 EN 3.2

5.3

Control terminals

ECSXA070

Fig. 5−7

Plug connectors for control terminals (X6)

For the supply of the control electronics an external 24 V DC voltage at terminals X6/+24
and X6/GND is required.

(

Stop!

ƒ

The control cables must always be shielded to prevent interference
injections.

ƒ

The voltage difference between X6/AG, X6/GND and PE of the axis module
may maximally amount to 50 V.

ƒ

The voltage difference can be limited by:
– overvoltage−limiting components or
– direct connection of X6/AG and X6/GND to PE.

ƒ

The wiring has to ensure that for X6/DO1 = 0 (LOW level) the connected axis
modules do not draw energy from the DC bus. Otherwise, the power supply
module may be damaged.