Monitoring functions

Configuring monitoring functions

Monitoring of internal device temperature (OH1, OH5)

10

l

209

EDBCSXA064 EN 3.2

10.3.7

Monitoring of internal device temperature (OH1, OH5)

The temperature inside the controller can be monitored with two temperature thresholds:

ƒ

Adjustable threshold (OH5)
– The warning threshold can be set under C0124
– The reaction to exceeding the threshold can be set under C0605

ƒ

Fixed threshold (OH1)
– Threshold = 90 °C
– Reaction to exceeding the threshold = TRIP

The hysteresis is 5 K, i.e. the reset value for the fixed warning threshold is 85 °C.

The monitoring with the adjustable threshold (OH4) is designed as an early warning stage
before final disconnection of the controller by means of TRIP (OH). Therefore, the process
can be influenced accordingly, so that the final disconnection of the controller at
unfavourable moments is avoided. Furthermore, for instance, additional fans can be
activated, generating a noise load when switched to continuous operation.

Code

Possible settings

IMPORTANT

No.

Designation

Lenze/
{Appl.}

Selection

C0124 OH5 limit

75

Threshold for temperature
monitoring inside the device

^ 209

10

{1 %}

90 C0062 > C0124

ð fault message

OH5 (C0605)

C0605 MONIT OH5

2

Fault response − monitoring of
temperature inside the
controller.
Temperature threshold can be
set under C0124.

^ 209

0

TRIP

2

Warning

3

Off