Electrical installation

Power terminals

5

l

63

EDBCSXA064 EN 3.2

Shielded cables

The following factors decisively determine the effect of the shielded cables:

ƒ

Good shield connection
– Ensure a contact surface as large as possible

ƒ

Low shield resistance
– Only use shields with tin−plated or nickel−plated copper braids (shields with steel

braids cannot be used).

ƒ

High overlap rate of the braid
– At least 70 ... 80 % with 90° overlap angle

The ECSZS000X0B shield mounting kit includes a wire clamp and shield sheet.