Connection to the DC bus (+U

G

, −U

G

)

(

Stop!

No device protection for DC bus voltage surges
In passive axis modules (without 24 V−supply), the charging circuit can be
overloaded through DC bus voltage surges.
Possible consequences:

ƒ

Destruction of the device

Protective measures:

ƒ

All axis modules in the DC−bus connection should be basically supplied with
a control voltage of 24 V.

ƒ

If the total cable length is > 20 m, install an axis module or a capacitor module
directly at the power supply module.

ƒ

Design the ±U

G

cables twisted and as short as possible. Ensure short−circuit−proof

routing!

ƒ

Cable length (module

« module) > 30 cm: install shielded ±U

G

cables.

Cable cross−section

Cable length
(module/
module)

Wire end ferrule

Cable cross−section Tightening torque

Stripping length

Up to 20 m

Without wire end
ferrule

6 mm

2

(AWG 10)

1.2 ... 1.5 Nm

(10.6 ... 13.3 lb−in)

5 mm for screw
connection

10 mm for spring
connection

With insulated wire end
ferrule

> 20 m

Without wire end
ferrule

10 mm

2

(AWG 8)

With insulated wire end
ferrule
Use pin−end connectors
for wiring!