System modules

CAN_Management (node number 101)
Status messages

13

l

280

EDBCSXA064 EN 3.2

13.6.5

Status messages

The SB CAN_Management provides different status messages which can be processed in
the PLC program:

Identifiers

Information

CAN_bCe1CommErrCanIn1_b

TRUE CAN1_IN communication error

CAN_bCe2CommErrCanIn1_b

TRUE CAN2_IN communication error

CAN_bCe3CommErrCanIn1_b

TRUE CAN3_IN communication error

CAN_bCe4BusOffState_b

TRUE CAN bus "Off State" detected (CAN bus interface X4)

CAN_bFreePdoTxBufferOverflow
_b

Free CAN objects

TRUE Overflow of the transmit request memory

CAN_bFreePdoRxOverflow_b

Free CAN objects

TRUE Overflow of the receipt memory

CAN_bOverrunLifeTime_b

CAN monitoring mechanism "Node Guarding"

TRUE "Life Guarding Event":

The controller configured as CAN slave does not receive a "Node
Guarding" telegram with the "Node Life Time" from the CAN
master.

CAN_byNodeAddress

1 ... 63 Node address (CAN bus interface X4)

CAN_byState

CAN bus operating status (CAN bus interface X4)

1 Operational

2 Pre−Operational

3 Warning

4 Bus off