System bus (CAN / CAN−AUX) configuration

Remote parameterisation (gateway function)

8

l

181

EDBCSXA064 EN 3.2

IMPORTANT

Possible settings

Code

Selection

Lenze/
{Appl.}

Designation

No.

C0603 MONIT CE5

3

Fault response − gateway
function monitoring (CE5)
"Timeout" when remote
parameter setting (C0370) is
activated via interface X4 (CAN)

^ 202

^ 180

0

TRIP

2

Warning

3

Off

C2118 ParWriteChan

.

0

CAN object for L_ParRead and
L_ParWrite
(byComChannel = 10)

^ 180

0

Unused PDO channel free for
reconfiguration
(CAN1...3_IN/CAN1...3_OUT)

1

Parameter data channel 2

C2470 ParWrite

0

CANaux channel used by
L_ParWrite/L_ParRead
(byComChannel = 11)

^ 180

0

Unused PDO channel free for
reconfiguration
(CANaux1...3_IN/CANaux1...3_OUT)

1

Parameter data channel 2

C2485 MONIT CE15

3

Fault response − gate function
monitoring (CE15)
"Timeout" when remote
parameterisation (C0370) is
activated via interface X14
(CAN−AUX)

^ 202

^ 180

0

TRIP

2

Warning

3

Off