Commissioning

Controller enable (CINH = 0)

6

l

131

EDBCSXA064 EN 3.2

6.11

Controller enable (CINH = 0)

The controller will only be enabled internally if no signal sources relevant for the controller
inhibit (CINH) are activated (i.e. CINH−signal sources = 0).

The following table shows the signal sources for controller enable:

Source for controller
inhibit

Controller
inhibit

Controller
enable

Note

Terminal X6/SI1

0 ... +4 V
(LOW level)

+13 ... +30 V
(HIGH level)

For controller enable, X6/SI1 has to be
= HIGH and X6/SI2 = HIGH.

Terminal X6/SI2

0 ... +4 V
(LOW level)

+13 ... +30 V
(HIGH level)

C0040

C0040 = 0

C0040 = 1

Operating
module/keypad

s key

u key

Inhibiting with

s key is only possible if

the

s key is assigned with "CINH" via

C0469.

Fault

l

In case of TRIP

l

In case of
message

l

No TRIP/message
active

l

TRIP reset

For check see

^ 236.

Control word −
system bus (CAN),
C0135

C0135/bit 9 = 1

C0135/bit 9 = 0

GDC function keys:

l

<F8> key (controller enable/start)

l

<F9> key (controller inhibit/stop)

Fieldbus module

See Operating Instructions of the corresponding fieldbus module.

)

Note!

All signal sources act like a series connection of switches which are
independent of each other.