Appendix – Lenze ECSCAxxx User Manual

Page 425

Advertising
background image

Appendix

Code table

14

l

425

EDBCSXA064 EN 3.2

IMPORTANT

Possible settings

Code

Selection

Lenze/
{Appl.}

Designation

No.

C2453

Source for system bus node
addresses of
CANaux_IN/CANaux_OUT (CAN
bus interface X14)

^ 160

1 CANa addr sel

0

CAN node address (C2450)

Address CANaux1_IN/OUT

2 CANa addr sel

0

CAN node address (C2450)

Address CANaux2_IN/OUT

3 CANa addr sel

0

CAN node address (C2450)

Address CANaux3_IN/OUT

0

C2450 (auto)

Automatically determined by
C2450

1

C2454 (man.)

Determined by C2454

C2454

Alternative node addresses for
CANaux_IN/CANaux_OUT (CAN
bus interface X14)

^ 160

1 CANa addr.

129

1

{1}

512 CANaux1_INaddress 2

2 CANa addr.

1

CANaux1_OUTaddress 2

3 CANa addr.

257

CANaux2_INaddress 2

4 CANa addr.

258

CANaux2_OUTaddress 2

5 CANa addr.

385

CANaux3_IN address 2

6 CANa addr.

386

CANaux3_OUT address 2

C2455

Identifier for
CANaux_IN/CANaux_OUT (CAN
bus interface X14)
Read only

^ 458

1 CANa Id

1

{1}

2047 Identifier CANaux1_IN

2 CANa Id

Identifier CANaux1_OUT

3 CANa Id

Identifier CANaux2_IN

4 CANa Id

Identifier CANaux2_OUT

5 CANa Id

Identifier CANaux3_IN

6 CANa Id

Identifier CANaux3_OUT

C2456

CAN time settings for CAN bus
interface X14 (CAN−AUX)

^ 163

1 CANa times

3000

0

{1 ms}

65000 CAN−AUX boot−up time:

Delay time after mains
connection for initialisation
through the master.

2 CANa times

0

CANaux2...3_OUT cycle times:
Factor for the task time to send
process data telegram.
0 = event−controlled
transmission

3 CANa times

0

4 CANa times

20

Delay time for initial
transmission of the process data
objects 2 and 3 after the CAN bus
changed to "Operational"

C2457

Monitoring time for
CANaux1...3_IN (CAN bus
interface X14)

^ 202

1 CE monit time

3000

1

{1 ms}

65000 CE11 monitoring time

2 CE monit time

3000

CE12 monitoring time

3 CE monit time

3000

CE13 monitoring time

Advertising
This manual is related to the following products: