Troubleshooting and fault elimination, Fault messages causes and remedies – Lenze ECSCAxxx User Manual

Page 248

Advertising
background image

Troubleshooting and fault elimination

Fault messages
Causes and remedies

12

l

248

EDBCSXA064 EN 3.2

Remedy

Cause

Description

Fault message

Remedy

Cause

Description

Display

No.

x062

CE1

Communication error on the
process data input object
CAN1_IN

CAN1_IN object receives faulty
data or communication is
interrupted.

l

Check wiring at X4.

l

Check sender.

l

Increase monitoring time
under C0357/1, if necessary.

l

Switch off monitoring
(C0591 = 3).

x063

CE2

Communication error on the
process data input object
CAN2_IN

CAN2_IN object receives faulty
data or communication is
interrupted.

l

Check wiring at X4.

l

Check sender.

l

Increase monitoring time
under C0357/2, if necessary.

l

Switch off monitoring
(C0592 = 3).

x064

CE3

Communication error on the
process data input object
CAN3_IN

CAN3_IN object receives faulty
data or communication is
interrupted.

l

Check wiring at X4.

l

Check sender.

l

Increase monitoring time
under C0357/3, if necessary.

l

Switch off monitoring
(C0593 = 3).

x065

CE4

BUS−OFF state of system
bus (CAN), interface X4

The module has received too
many incorrect telegrams via the
system bus (CAN) and has
disconnected from the bus

l

Check wiring at X4: bus
termination available?

l

Check screen contact of the
cables.

l

Check PE connection.

l

Check bus load, reduce baud
rate, if necessary (Observe
cable length!)

l

Switch off monitoring
(C0595 = 3).

x066

CE5

System bus (CAN) time−out
(communication error of gateway
function), interface X4

For remote parameterisation
(C0370, C0371) via system bus
(CAN):

l

Slave does not respond.

l

Communication monitoring
time has been exceeded.

l

Check wiring at X4.

l

Check CAN bus configuration.

l

Switch off monitoring
(C0603 = 3).

0070

U15

Undervoltage of internal 15 V
voltage supply

Check voltage supply.

0071

CCr

System failure

Strong interference injection on
the control cables

Screen control cables

Ground or earth loops in the
wiring

l

Check wiring

l

Check PE connection

After troubleshooting: Deenergise
the device completely (disconnect
24 V supply, discharge DC bus)!

0072

PR1

Checksum error in parameter
set 1
CAUTION: The Lenze setting is
loaded automatically!

l

Fault when loading a
parameter set.

l

Interruption while
transmitting the parameter set
via keypad.

l

Set the required parameters
and store them under C0003 =
1.

l

As to PLC devices, check the
use of pointers.

The stored parameters are
incompatible with the loaded
software version.

Store the parameter set under
C0003 = 1 first to allow for a
faults reset.

x: 0 = TRIP, 1 = Message, 2 = Warning, 3 = FAIL−QSP