Troubleshooting and fault elimination, Fault messages causes and remedies – Lenze ECSCAxxx User Manual

Page 247

Advertising
background image

Troubleshooting and fault elimination

Fault messages

Causes and remedies

12

l

247

EDBCSXA064 EN 3.2

Remedy

Cause

Description

Fault message

Remedy

Cause

Description

Display

No.

0051

OH1

Interior temperature > +90

°C

Ambient temperature
T

u

> +40

°C or > +50 °C

l

Allow module to cool and
ensure better ventilation.

l

Check ambient temperature in
the control cabinet.

Wrong mounting position

Change mounting position.

x053

OH3

Motor temperature
> +150

°C threshold

(temperature detection via
resolver or incremental value
encoder)

Motor is thermally overloaded
due to:

l

Impermissible continuous
current

l

Frequent or too long
acceleration processes

l

Check drive dimensioning.

l

Switch off monitoring
(C0583 = 3).

No PTC/temperature contact
connected.

Correct wiring.

x054

OH4

Heatsink temperature > C0122

Ambient temperature T

u

> +40

°C

or > +50

°C

l

Allow module to cool and
ensure better ventilation.

l

Check ambient temperature in
the control cabinet.

l

Switch off monitoring
(C0582 = 3).

Heatsink is very dirty.

Clean heatsink

Wrong mounting position

Change mounting position.

The value specified under C0122
is set too low.

Enter a higher value under C0122.

x055

OH5

Interior temperature > C0124

l

Allow module to cool and
ensure better ventilation.

l

Check ambient temperature in
the control cabinet.

l

Switch off monitoring
(C0605 = 3).

The value under C0124 is set too
low.

Enter a higher value under C0124.

x057

OH7

Motor temperature > C0121
(temperature detection via
resolver or incremental value
encoder)

Motor is thermally overloaded
due to:

l

Impermissible continuous
current

l

Frequent or too long
acceleration processes

l

Check drive dimensioning.

l

Switch off monitoring
(C0584 = 3).

No PTC/temperature contact
connected.

Correct wiring.

The value specified under C0121
is set too low.

Enter a higher value in C0121.

x058

OH8

Motor temperature via inputs T1
and T2 is too high.

Motor is thermally overloaded
due to:

l

Impermissible continuous
current

l

Frequent or too long
acceleration processes

l

Check drive dimensioning.

l

Switch off monitoring
(C0585 = 3).

Terminals T1 and T2 are not
connected

Connect PTC/temperature
contact.

x061

CE0

Automation interface (AIF)
communication error

Faulty transfer of control
commands via AIF.

l

Plug in the communication
module/keypad XT firmly,
screw down, if necessary.

l

Switch off monitoring
(C0126 = 3).

x: 0 = TRIP, 1 = Message, 2 = Warning, 3 = FAIL−QSP

Advertising
This manual is related to the following products: