Preface and general information

System block introduction

Definition of the inputs/outputs

1

l

25

EDBCSXA064 EN 3.2

Example:

Use of the system blocks Inputs_Digital and Outputs_Digital

C0443

X6

Inputs_DIGITAL

DI3

SI1

SI2

DI1

DI4

DI2

safe standstill

1

0

C0114/1...4

1

X6

C0443

mP

mP + Imp

DIGIN_bIn1_b

DIGIN_bIn2_b

DIGIN_b_safe_standstill_b

DIGIN_bIn4_b

DIGIN_bIn3_b

DIGIN_bCInh_b

POE

Outputs_DIGITAL

X6

X6

1

0

C0118/1

DO1

SO

1

B-

B2

B+

1

0

C0118/2

1

B1

X25

X6

safe torque off

C0444/1

C0444/2

C0602

MONIT-Rel1

DIGOUT_bOut1_b

DIGOUT_bRelais_b

ECSXA207

Fig. 1−2

Plan: connecting the system blocks "Inputs_Digital" and "Outputs_Digital"

If you want to use digital input 1 and digital output 1, carry out the following steps:

1. Explicitly integrate the system blocks Inputs_DIGITAL and Outputs_DIGITAL into the

control configuration of the DDS. (

26)

2. For access to digital input 1:

– Assign the system variable DIGIN_bIn1_b to a POU variable.

3. For access to digital output 1:

– Assign the system variable DIGOUT_bOut1_b to a POU variable.

)

Note!

According to the IEC 61131−3 standard the system variables DIGIN_bIn1_b and
DIGOUT_bOut1_b may generally only be used once.
The use of one system variable in several POUs must be carried out via a copy
(as global variable).