1 digital inputs and outputs, Digital inputs and outputs, Electrical installation – Lenze ECSCAxxx User Manual

Page 78: Stop

Advertising
background image

Electrical installation

Control terminals
Digital inputs and outputs

5

l

78

EDBCSXA064 EN 3.2

5.3.1

Digital inputs and outputs

(

Stop!

If an inductive load is connected to X6/DO1, a spark suppressor with a limiting
function to max. 50 V

± 0 % must be provided.

DI1 DI2 DI3 DI4

47k

GNDext

3k3

3k3

3k3

3k3

GND

DO1

X6

1.5

A

1k

+

_

24 VDC =

+24

"

"

ECSXA014

Fig. 5−9

Digital inputs and outputs at X6

"

HF−shield termination by large−surface connection to functional earth (see Mounting
Instructions for ECSZS000X0B shield mounting kit)

ƒ

The digital inputs X6/DI1 ... DI4 are freely assignable.

ƒ

The polarity of the digital inputs X6/DI1 ... DI4 is set under C0114/x.

ƒ

The polarity of the digital output (X6/DO1) is set under C0118/1.