AIF interface (X1) configuration

Operating status of AIF interface

9

l

195

EDBCSXA064 EN 3.2

9.9

Operating status of AIF interface

C2121 serves to display the operating status of the AIF interface X1:

Code

Possible settings

IMPORTANT

No.

Designation

Lenze/ap
pl.

Selection

C2121 AIF:State

AIF status
More detailed information can
be found in the documentation
of the plugged−in fieldbus
module.
Read only

^ 195

1

{1}

255 Binary interpretation reflects bit

states.

Bit 0

XCAN1_IN monitoring time

Bit 1

XCAN2_IN monitoring time

Bit2

XCAN3_IN monitoring time

Bit3

XCAN bus off

Bit4

XCAN operational

Bit5

XCAN pre−operational

Bit 6

XCAN warning

Bit 7

Assigned internally

C2121

Bits 3 ... 6

Operating state

Description

Bit 3 = 1

Bus off

The ECSxA... axis module has been decoupled from the system bus due to
too many faulty telegrams received.

l

The response to this status can be configured via C2382/4.

^ 193

Bit 4 = 1

Operational

The system bus is fully operational. The ECSxA... axis module can transmit
and receive parameter and process data.

Bit 5 = 1

Pre−operational

The ECSxA... axis module can transmit and receive parameter data.
Process data, however, are ignored.
The Pre−Operational status can be changed to Operational status by:

l

CAN master

l

a reset node (

^ 191)

l

the "Pre−Operational to Operational" NMT command

Bit 6 = 1

Warning

The ECSxA... axis module has received faulty telegrams and participates
only passively in the system bus, i.e. the axis module no longer transmits
any data.
Possible causes:

l

Missing bus termination

l

Insufficient shielding

l

Potential differences in the grounding of the control electronics

l

Excessive bus load

l

The ECSxA... axis module is not connected to the system bus.