Appendix, Code table – Lenze ECSCAxxx User Manual

Page 404

Advertising
background image

Appendix

Code table

14

l

404

EDBCSXA064 EN 3.2

IMPORTANT

Possible settings

Code

Selection

Lenze/
{Appl.}

Designation

No.

[C0370] SDO gateway

0

Activate address
gateway/remote
parameterisation
The SDO gateway cannot be
used to read out codes >C2000
or codes of the Inverter Drives
8400 and Servo Drives 9400.

l

C0370

¹ 0: All code

write/read accesses are
redirected to the CAN node
with the CAN node address
set here.

l

The corresponding code is
accessed via parameter data
channel 1 of the target device.

l

C0370 = 0: remote
parameterisation is
deactivated

^ 180

0

{1}

63

C0371 Gateway Ch.

1

Selection of the gateway channel

^ 180

0

CAN

Use CAN bus interface X4

1

CAN−AUX

Use CAN bus interface X14

C0381 HeartProdTim

e

0

Heartbeat (slave):
HeartbeatProducerTime

l

Time interval for sending the
heartbeat message

l

Only relevant for setting
C0352 = 3.

0

{1 ms}

65535

C0382 GuardTime

0

Node Guarding (slave):
NodeGuardTime

l

Time interval of the status
inquiry of the master

l

Only relevant for setting
C0352 = 4.

^ 172

0

{1 ms}

65535

C0383 LifeTimeFact

0

Node Guarding (slave):
NodeLifeTime factor

l

Factor for the monitoring
time of NodeLifeTime

l

NodeLifeTime = C0383 x
C0382 (NodeGuardTime)

l

Only relevant for setting
C0352 = 4.

^ 172

0

{1}

255

C0384 Err

NodeGuard

3

Node Guarding (slave)

l

Response for the occurrence
of a NodeGuard−Event

l

Only relevant for setting
C0352 = 4.

^ 172

0

TRIP

1

Message

2

Warning

3

Off

4

FAIL−QSP

Advertising