2 outputs_aif3, Outputs_aif3, System modules – Lenze ECSCAxxx User Manual

Page 273: System variables

Advertising
background image

System modules

AIF3_IO_AutomationInterface (node number 43)

Outputs_AIF3

13

l

273

EDBCSXA064 EN 3.2

13.4.2

Outputs_AIF3

This SB is used as an interface for output signals (e.g. setpoints/actual values) to attached
fieldbus modules (e.g. INTERBUS, PROFIBUS−DP).

The process image is

ƒ

created in the cyclic task by means of a fixed set time interval of 10 ms.

ƒ

created in an interval task within the time set for this task.

ƒ

read at the beginning of the task and written at its end.

,

Please read the documentation for the connected fieldbus module.

...

Byte

1

Byte

2

Byte

3

Byte

4

Byte

5

Byte

6

Byte

7

Byte

8

...

16 Bit

LowWord

16 Bit

HighWord

16 Bit

16 binary

signals

16 Bit

16 binary

signals

16 Bit

16 Bit

Outputs_AIF3

X1

AIF3_nOutW2_a

AIF3_nOutW1_a

AIF3_bFDO0_b

AIF3_bFDO15_b

AIF3_bFDO16_b

AIF3_bFDO31_b

AIF3_nOutW4_a

AIF3_dnOutD1_p

AIF3_nOutW3_a

ECSXA206

Fig. 13−8

System block "Outputs_AIF3"

System variables

Variable

Data

type

Signal

type

Address

Display

code

Display

format

Notes

AIF3_nOutW1_a

Integer

analog

%QW43.0

˘

˘

AIF3_nOutW2_a

%QW43.1

AIF3_nOutW3_a

%QW43.2

AIF3_nOutW4_a

%QW43.3

AIF3_bFDO0_b

...

AIF3_bFDO15_b

BOOL

binary

%QX43.0.0

...

%QX43.0.15

˘

˘

AIF3_bFDO16_b

...

AIF3_bFDO31_b

%QX43.1.0

...

%QX43.1.15

AIF3_dnOutD1_p

Double
integer

position

%QD43.0

˘

˘

Advertising