Commissioning – Lenze ECSCAxxx User Manual

Page 142

Advertising
background image

Commissioning

Optimising the drive behaviour after start
Speed controller adjustment

6

l

142

EDBCSXA064 EN 3.2

Parameter setting

ƒ

Set the proportional gain (V

pn

) via C0070:

– Enter approx. 50 % of the speed setpoint (100 % = 16384 = n

max

).

– Increase C0070 until the drive becomes instable (pay attention to engine noises).
– Reduce C0070 until the drive runs stable again.
– Reduce C0070 to approx. half the value.

ƒ

In the PLC program, the MCTRL_nNAdapt_a variable can be used to change the
proportional gain (V

pn

):

– V

pn

= MCTRL_nNAdapt_a [%] × C0070

– Default: MCTRL_nNAdapt_a = 100 %

ð V

pn

= 100 % × C0070 = C0070

Code

Possible settings

IMPORTANT

No.

Designation

Lenze/
{Appl.}

Selection

C0070 Vp speedCTRL

3.0

Proportional gain of speed
controller (V

pn

)

^ 141

0.00

{ 0.01}

127.99

ƒ

The reset time (T

nn

) is set via C0071:

– Reduce C0071 until the drive becomes instable (pay attention to engine noises).
– Increase C0071 until the drive runs stable again.
– Increase C0071 to approx. the double value.

Code

Possible settings

IMPORTANT

No.

Designation

Lenze/
{Appl.}

Selection

C0071 Tn speedCTRL

24.0

Reset time − speed controller
(T

nn

)

^ 141

1.0

{0.5 ms}

6000.0

ƒ

The derivative gain (T

dn

) is set via C0072:

– Increase C0072 during operation until an optimal control mode is reached,

although the D component is mostly not used in praxis (C0072=0).

Code

Possible settings

IMPORTANT

No.

Designation

Lenze/
{Appl.}

Selection

C0072 Td speedCTRL

0.0

Derivative gain of speed
controller (T

dn

)

^ 141

0.0

{0.1 ms}

32.0

Advertising