Troubleshooting and fault elimination, Fault messages causes and remedies – Lenze ECSCAxxx User Manual

Page 251

Advertising
background image

Troubleshooting and fault elimination

Fault messages

Causes and remedies

12

l

251

EDBCSXA064 EN 3.2

Remedy

Cause

Description

Fault message

Remedy

Cause

Description

Display

No.

x091

EEr

External monitoring has been
triggered via DCTRL.

A digital signal assigned to the
TRIP−SET function has been
activated.

l

Check external encoder.

l

Switch off the monitoring
(C0581 = 3).

x095

FAN1

Fan monitoring
(for built−in units)

Heatsink fan is locked, dirty or
defect.

Clean or exchange heatsink fan.

0105

H05

Internal fault (memory)

Contact Lenze.

0107

H07

Internal fault (power stage)

During initialisation of the
controller, an incorrect power
stage was detected.

Contact Lenze.

x108

H08

"Extension board" error

"Extension board" not connected
correctly.

l

Connect "extension board"
correctly.

l

Check connector.

"Extension board" is not
supported by PLC program.

l

Adapt PLC program to
"extension board".

l

Use "extension board" which is
supported by PLC program.

x110

H10

Heatsink temperature sensor
error

Sensor for detecting the heatsink
temperature indicates undefined
values.

l

Contact Lenze.

l

Switch off the monitoring
(C0588 = 3).

x111

H11

Temperature sensor error:
Temperature inside the controller

Sensor for detecting the internal
temperature indicates undefined
values.

l

Contact Lenze.

l

Switch off the monitoring
(C0588 = 3).

x122

CE11

Communication error at the
process data input object
CANaux1_IN

CANaux1_IN object receives
faulty data or communication is
interrupted.

l

Check wiring at X14.

l

Check transmitter.

l

Increase monitoring time
under C2457/1, if necessary.

l

Switch off monitoring
(C2481 = 3).

x123

CE12

Communication error at the
process data input object
CANaux2_IN

CANaux2_IN object receives
faulty data or communication is
interrupted.

l

Check wiring at X14.

l

Check transmitter.

l

Increase monitoring time
under C2457/2, if necessary.

l

Switch off monitoring
(C2482 = 3).

x124

CE13

Communication error at the
process data input object
CANaux3_IN

CANaux3_IN object receives
faulty data or communication is
interrupted.

l

Check wiring on X14.

l

Check transmitter.

l

Increase monitoring time
under C2457/3, if necessary.

l

Switch off monitoring
(C2483 = 3).

x125

CE14

BUS−OFF state of system
bus (CAN), interface X14

The module has received too
many incorrect telegrams via the
system bus (CAN) and has
disconnected from the bus

l

Check wiring at X14: bus
termination available?

l

Check screen contact of the
cables.

l

Check PE connection.

l

Check bus load, reduce baud
rate, if necessary (Observe
cable length!)

l

Switch off monitoring
(C2484 = 3).

x126

CE15

Communication error of the
gateway function via interface
X14 (CAN−AUX)

l

C0371 = 1: Gateway channel
X14 (CAN−AUX)

l

C2470: Selection of the
CANaux object for L_ParRead
and L_ParWrite

l

Slave does not respond.

l

Communication monitoring
time has been exceeded.

l

Check wiring at X14.

l

Check CAN bus configuration.

l

Switch off monitoring
(C2485 = 3).

x: 0 = TRIP, 1 = Message, 2 = Warning, 3 = FAIL−QSP