Monitoring functions

Configuring monitoring functions
Time−out monitoring for activated remote parameterisation

10

l

204

EDBCSXA064 EN 3.2

10.3.2

Time−out monitoring for activated remote parameterisation

If remote parameterisation is activated (gateway function (

180)) and a timeout occurs,

the system error message CE5/CE15 is output.

The response to this can be configured via C0603/C2485.

Code

Possible settings

IMPORTANT

No.

Designation

Lenze/
{Appl.}

Selection

C0603 MONIT CE5

3

Fault response − gateway
function monitoring (CE5)
"Timeout" when remote
parameter setting (C0370) is
activated via interface X4 (CAN)

^ 202

^ 180

0

TRIP

2

Warning

3

Off

C2485 MONIT CE15

3

Fault response − gate function
monitoring (CE15)
"Timeout" when remote
parameterisation (C0370) is
activated via interface X14
(CAN−AUX)

^ 202

^ 180

0

TRIP

2

Warning

3

Off