Troubleshooting and fault elimination

Fault analysis

Fault analysis via LECOM status words (C0150/C0155)

12

l

239

EDBCSXA064 EN 3.2

12.1.4

Fault analysis via LECOM status words (C0150/C0155)

The LECOM status words (C0150/C0155) are coded as follows:

Code

Possible settings

IMPORTANT

No.

Designation

Lenze/
{Appl.}

Selection

C0150 Status word

0

Device status word 1 (DCTRL)
Read only

^ 328

^ 239

0

{1}

65535 Controller evaluates information

as 16 bits (binary−coded)

Bit 0

Not assigned

DCTRL_bStateB0_b

Bit 1

Pulse inhibit (IMP)

DCTRL_bImp_b

Bit2

Not assigned

DCTRL_bStateB2_b

Bit3

Not assigned

DCTRL_bStateB3_b

Bit4

Not assigned

DCTRL_bStateB4_b

Bit5

Not assigned

DCTRL_bStateB5_b

Bit 6

n = 0

DCTRL_bNActEq0_b

Bit 7

Controller inhibit (CINH)

DCTRL_bCInh_b

Bit 8

Device status bit 1

DCTRL_bStat1_b

Bit 9

Device status bit 2

DCTRL_bStat2_b

Bit10

Device status bit 3

DCTRL_bStat4_b

Bit11

Device status bit 4

DCTRL_bStat8_b

Bit12

Warning

DCTRL_bWarn_b

Bit13

Message

DCTRL_bMess_b

Bit14

Not assigned

DCTRL_bStateB14_b

Bit15

Not assigned

DCTRL_bStateB15_b

The status bits 8 ... 11 in C0150 display the binary−coded device status of the axis module:

Status bit 11

Status bit 10

Status bit 9

Status bit 8

Description

0

0

0

0

Initialisation after connecting the
supply voltage

0

0

0

1

Switch−on inhibit / restart
protection active (C0142 = 0)

0

0

1

1

Controller inhibited

0

1

1

0

Controller enabled

0

1

1

1

A monitoring function returns a
"message".

1

0

0

0

A monitoring function returns a
"TRIP".

1

0

1

0

A monitoring function returns a
"FAIL−QSP".

0 = FALSE

1 = TRUE