Monitoring functions

Configuring monitoring functions

Current load of controller (I x t monitoring: OC5, OC7)

10

l

213

EDBCSXA064 EN 3.2

The maximum admissible overcurrent is dependent on the I

max

limit set in C0022.

 I

max

limit set in C0022

£ 150 % I

r

:

ƒ

For 180 s, the arithmetic mean value of the motor current must not exceed 100 % of
the rated device current.

ƒ

Example: Arithmetic mean for characteristic

:

60 s @ 150 % ) 120 s @ 75 %

180 s

+ 100 %

‚ I

max

limit set in C0022 > 150 % I

r

:

ƒ

For 60 s, the arithmetic mean value of the motor current must not exceed 70 % of
the rated device current.

ƒ

Example: Arithmetic mean for characteristic

‚:

10 s @ 200 % ) 50 s @ 44 %

60 s

+ 70 %

The current device utilisation is displayed in C0064:

Code

Possible settings

IMPORTANT

No.

Designation

Lenze/
{Appl.}

Selection

C0064 Utilization

Device utilisation (I x t) over the
last 180 s
Only display

0

{1 %}

150

l

C0064 > 100 % activates
OC5−TRIP.

l

TRIP−RESET only is possible if
C0064 < 95 %.