System modules

AIF_IO_Management (node number 161)

Inputs_AIF_Management

13

l

255

EDBCSXA064 EN 3.2

13

System blocks

13.1

AIF_IO_Management (node number 161)

13.1.1

Inputs_AIF_Management

This SB serves to monitor the communication of a fieldbus module connected to the
automation interface (AIF).

ƒ

In the event of an error, AIF_bCe0CommErr_b is set to TRUE and the communication
error "CE0" (LECOM no. 61) is set. The response to this can be configured via C0126
(default setting: off).

ƒ

New AIF fielbus modules (e. g. 2133 and 2175) also use
AIF_bFieldBusStateBit0_b ... AIF_bFieldBusStateBit15_b to transfer an error number
from the fieldbus module.

ƒ

C2121 serves to display the status.

,

Please read the documentation for the connected fieldbus module.

AIF

Communication

Error

AIF

Fieldbus State

X1

Inputs_AIF_Management

AIF_bCe0CommErr_b

AIF_bFieldBusStateBit0_b

AIF_bFieldBusStateBit1_b

AIF_bFieldBusStateBit2_b

AIF_bFieldBusStateBit6_b

AIF_bFieldBusStateBit5_b

AIF_bFieldBusStateBit4_b

AIF_bFieldBusStateBit3_b

AIF_bFieldBusStateBit7_b

AIF_bFieldBusStateBit8_b

AIF_bFieldBusStateBit9_b

AIF_bFieldBusStateBit10_b

AIF_bFieldBusStateBit14_b

AIF_bFieldBusStateBit13_b

AIF_bFieldBusStateBit12_b

AIF_bFieldBusStateBit11_b

AIF_bFieldBusStateBit15_b

ECSXA200

Fig. 13−1

System block "Inputs_AIF_Management"