AIF interface (X1) configuration

Cycle time (XCAN1_OUT ... XCAN3_OUT)

9

l

188

EDBCSXA064 EN 3.2

9.5

Cycle time (XCAN1_OUT ... XCAN3_OUT)

The transfer of the output data of XCAN1_OUT ... XCAN3_OUT can be event or
time−controlled.

The transmission mode can be configured via code C2356/x:

Code

Possible settings

IMPORTANT

No.

Designation

Lenze/ap
pl.

Selection

C2356

Time settings for XCAN
(AIF interface X1)

^ 188

1 XCAN times

0

0

{1 ms}

65000 XCAN boot−up time:

Delay time for initialisation
through the master after mains
connection.

2 XCAN times

0

XCAN1...3_OUT cycle times:
Factor for the task time to send
process data object.
0 = event−controlled
transmission

3 XCAN times

0

4 XCAN times

0

5 XCAN times

0

Delay time for initial
transmission of the process data
objects after the NMT status
changed to "Operational"

Event−controlled transmission

C2356/x = 0

ƒ

The output data is always transferred when one value in the eight bytes of user data
has changed (Lenze default setting).

Time−controlled transmission

C2356/x = 1 ... 65000

ƒ

The output data is transferred with the cycle time set in C2356/x (referred to the
task cycle time).

Example:

ƒ

The CAN object is used in a 10 ms task.

ƒ

Factor set via C0356/2 = 5

ðThe CAN object is sent in every fifth task cycle, hence every 50 ms (10 ms x 5).