System modules

ANALOG1_IO (node number 11)

Inputs_ANALOG1 (analog input)

13

l

275

EDBCSXA064 EN 3.2

13.5

ANALOG1_IO (node number 11)

13.5.1

Inputs_ANALOG1 (analog input)

This SB represents the interface for analog differential signals via terminal X6/AI+, AI− as
a setpoint input or an actual value input.

AI-

AI+

AG

X6

C0034

C0026/1

C0400

C0027/1

AIN1_bError_b

AIN1_nIn_a

Inputs_ANALOG1

ECSXA221

Fig. 13−9

System block "Inputs_ANALOG1"

Analog input configuration

ƒ

Use C0034 to set whether the input is to be used for a master voltage (

±10 V) or a

master current (+4 ... 20 mA or

±20 mA).

ƒ

Set jumper bar X3 according to the setting in C0034:

(

Stop!

Do not plug the jumper on the pins 3−4! The axis module cannot be initialised
like this.

Jumper bar X3

Setting

Measuring range

6
4
2

5
3

1

5−6 open

Jumper on 1−2: Parking position

C0034 = 0 (master voltage)

l

Level: −10 ... +10 V

l

Resolution: 5 mV (11 bits + sign)

l

Scaling:

±10 V º ±16384 º ±100 %

6
4
2

5
3

1

5−6 closed

C0034 = 1 (master current)

l

Level: +4 ... +20 mA

l

Resolution: 20

mA (10 bits without sign)

l

Scaling:

+4 mA º 0 º 0 %

+20 mA º 16384 º 100 %

C0034 = 2 (master current)

l

Level: −20 ... +20 mA

l

Resolution: 20

mA (10 bits + sign)

l

Scaling:

±20 mA º ±16384 º ±100 %

Use as master current input

ƒ

Master current < 2 mA:
– Variable AIN1_bError_b = TRUE
– An error handling can be set via C0598.

ƒ

Master current >= 2 mA:
– Variable AIN1_bError_b = FALSE