1 settings via dip switch, Settings via dip switch, System bus (can / can−aux) configuration – Lenze ECSCAxxx User Manual

Page 156

Advertising
background image

System bus (CAN / CAN−AUX) configuration

Setting the CAN node address and baud rate
Settings via DIP switch

8

l

156

EDBCSXA064 EN 3.2

8.1.1

Settings via DIP switch

ECS_COB005

Fig. 8−1

DIP switch for node address and baud rate (all switches: OFF)

Node address setting

The node address is set by means of switches 2 ... 7 of the DIP switch. Specific values are
assigned to the switches. The sum of the values specifies the node address to be set (see
example).

Switch

Value

Example

Switching status

Node address

ON

OFF

ON

1

6

2

7

4

3

8

5

91

0

S1

OFF: Node address setting is only valid for CAN
(C0350 is overwritten if one of switches S2 ... S7
is in ON position.)
ON: Node address setting is valid for CAN and
CANaux (C0350 and C2450 are overwritten if
one of switches S2 ... S7 is in ON position.)

S2

32

ON

32 + 16 + 8 = 56

S3

16

ON

S4

8

ON

S5

4

OFF

S6

2

OFF

S7

1

OFF

Advertising
This manual is related to the following products: