Appendix – Lenze ECSCAxxx User Manual

Page 406

Advertising
background image

Appendix

Code table

14

l

406

EDBCSXA064 EN 3.2

IMPORTANT

Possible settings

Code

Selection

Lenze/
{Appl.}

Designation

No.

[C0419] Enc. setup

110

Encoder selection

l

Selection of encoder type
indicated on the nameplate of
the Lenze motor.

l

The encoder data (C0420,
C0421, C0427) is set
automatically in accordance
with the selection.

^ 331

^ 115

^ 122

0

Common

110

IT512−5V

Incremental encoder with TTL
level

111

IT1024−5V

112

IT2048−5V

113

IT4096−5V

210

IS512−5V

SinCos encoder

211

IS1024−5V

212

IS2048−5V

213

IS4096−5V

307

AS64−8V

SinCos absolute value encoder
with Hiperface® interface
(single−turn)
Selections 307, 308, 309 are only
possible with operating system
7.0 or higher.

308

AS128−8V

309

AS256−8V

310

AS512−8V

311

AS1024−8V

407

AM64−8V

SinCos absolute value encoder
with Hiperface® interface
(multi−turn)
Selections 407, 408, 409 are only
possible with operating system
7.0 or higher.

408

AM128−8V

409

AM256−8V

410

AM512−8V

411

AM1024−8V

[C0420] Encoder const.

512

Number of increments of the
encoder

^ 331

^ 115

^ 122

1

{1 inc/rev}

8192 Sets C0419 = 0 ("common") if the

value is altered.

[C0421] Encoder volt

0

Encoder voltage

^ 331

^ 115

^ 122

0

5.0 V

Sets C0419 = 0 ("common") if the
value is altered.

1

5.6 V

2

6.3 V

3

6.9 V

4

7.5 V

5

8.1 V

C0426 DIS: In

Signal at DFIN input
Only display

^ 331

−32767

{1 rpm}

32767

[C0427] Enc. signal

0

Function of the master frequency
input signals on X8 (DFIN)

^ 331

^ 115

^ 122

0

2−phase

1

A: speed
B: direction

2

A or B: speed or direction