Bulletin 283 Programmable Parameters

4-17

Not available on the Bulletin 283A.

On-to-Off Delay

This parameter allows the
installer to program a time
duration before an input is
reported “OFF”

Parameter Number

31

Access Rule

GET/SET

Data Type

UINT

Group

User I/O

Units

ms

Minimum Value

0

Maximum Value

65.000

Default Value

0

In Sink/Source

This parameter allows the
installer to program the inputs to
be sink or source.

0=Sink
1=Source

Parameter Number

32

Access Rule

GET/SET

Data Type

BOOL

Group

User I/O

Units

Minimum Value

0

Maximum Value

1

Default Value

0

OutA Pr FltState

This parameter in conjunction
with Parameter 34 defines how
Output A will respond when a
protection trip occurs. When set
to “1”, Output A continues to
operate as command via the
network. When set to “0”, Output
A will open or close as
determined by setting in
Parameter 34

Parameter Number

33

Access Rule

GET/SET

Data Type

BOOL

Group

User I/O

Units

Minimum Value

0

Maximum Value

1

Default Value

0

OutA Pr FltValue

This parameter determines the
state the Out A assumes when a
trip occurs and Parameter 33 is
set to “0”
0 = Open
1 = Close

Parameter Number

34

Access Rule

GET/SET

Data Type

BOOL

Group

User I/O

Units

Minimum Value

0

Maximum Value

1

Default Value

0