Rockwell Automation 284 ArmorStart User Manual User Manual

Page 380

Advertising
background image

C-8

Bulletin 283 CIP Information

Table C.17 Instance 186 This is a “Read Only” Status Assembly

Table C.18 Instance 187 This is a “Read/Write” Assembly

Table C.19 Instance 189 This is a “Read Only” assembly

➊Reserved for Bulletin 283.

Table C.20 Instance 190 is the 1999-ZCIO Native Format Produced Assembly.

Standard Distributed Motor
Controller I/O Assemblies

Standard Distributed Motor Controller IO Assemblies are available
on all Starter Types.

Instance 186 — DeviceNet Status

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

I/O Idle

I/O Flt

Exp Flt

I/O Cnxn Exp Cnxn

1

ZIP4 FLT

ZIP4

CNXN

ZIP3 FLT

ZIP3

CNXN

ZIP2 FLT

ZIP2

CNXN

ZIP1 FLT

ZIP1

CNXN

Instance 187 — Starter Control Bits

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

User Out

B

User Out

A

Fault

Reset

Run Fwd

1

Reserved

Instance 189 Warning Status Bits

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

IO Warning

Control

Power

Warning

PR Warning

PL Warning

1

HW Warn

DN Warn

PI Warn

Instance 190 1799-ZCIO Native Format Produced Assembly

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Running Rev

Running Fwd

Warning

Tripped

Input 3

Input 2

Input 1

Input 0

1

Reserved

Logic Enable

Reserved

140M On

HOA

2

Reserved

User Out B

User Out A

Reserved

Run Fwd

3

Reserved

4

Net Out 8

Net Out 7

Net Out 6

Net Out 5

Net Out 4

Net Out 3

Net Out 2

Net Out 1

5

ZIP CCV (Low)

6

ZIP CCV (High)

Advertising
This manual is related to the following products: