Bulletin 280/281 Programmable Parameters

3-27

Starter Setup

Table 3.2

FLA Setting Ranges and Default Values (with indicated setting

precision)

% Therm Utilized

This parameter displays the
% Thermal Capacity used

Parameter Number

105

Access Rule

GET/SET

Data Type

USINT

Group

Starter Display

Units

% FLA

Minimum Value

0

Maximum Value

100

Default Value

0

FLA Setting

The motor’s full load current
rating is programmed in this
parameter

Parameter Number

106

Access Rule

GET/SET

Data Type

INT

Group

Starter Setup

Units

xx.x Amps

Minimum Value

See Table 3.2

Maximum Value

See Table 3.2

Default Value

See Table 3.2

FLA Current Range (A)

Default Value

Minimum Value

Maximum Value

0.24

1.2

0.24

0.5

2.5

0.5

1.1

5.5

1.1

3.2

16.0

3.2

Overload Class

This parameter allows the
installer to select the overload
class

1= Overload Class 10
2= Overload Class 15
3= Overload Class 20

Parameter Number

107

Access Rule

GET/SET

Data Type

USINT

Group

Starter Setup

Units

xx.x Amps

Minimum Value

1

Maximum Value

3

Default Value

1

OL Reset Level

This parameter allows the
installer select the % Thermal
Capacity which an overload can
be cleared

Parameter Number

108

Access Rule

GET/SET

Data Type

USINT

Group

Starter Setup

Units

% FLA

Minimum Value

0

Maximum Value

100

Default Value

75