Bulletin 284 Programmable Parameters for Volts per Hertz Controllers

5-23

Drvin DNFltState
This parameter, in conjunction with Parameter 52, defines how the Drive Digital
Inputs 1…2 will respond when a DeviceNet fault occurs. When set to 1, Drive
Digital Inputs 1…2 hold last state occurs. When set to 0, will go to DnFlt Value on
DN faults as determined by Parameter 52.
0 = Go to Fault Value
1 = Hold Last State

Parameter Number

51

Access Rule

GET/SET

Data Type

BOOL

Group

Drive DeviceNet

Units

Minimum Value

0

Maximum Value

1

Default Value

0

Drvin DNFlt Value
This parameter determines if the drive will be commanded in the event of a
DeviceNet fault.
0 = OFF
1 = ON

Parameter Number

52

Access Rule

GET/SET

Data Type

BOOL

Group

Drive DeviceNet

Units

Minimum Value

0

Maximum Value

1

Default Value

0

Drvin DNIdlState

This parameter, in conjunction with Parameter 54, defines how the Drive Digital
Input 1…2 will respond when a DeviceNet network is idle. When set to 1, hold to
last state occurs. When set to 0, will go to DnFlt Value on DN faults as determined
by Parameter 54.
0 = Go to Fault Value
1 = Hold Last State

Parameter Number

53

Access Rule

GET/SET

Data Type

BOOL

Group

Drive DeviceNet

Units

Minimum Value

0

Maximum Value

1

Default Value

0

StrtrDN IdlValue

This parameter determines the state that Digital Inputs 1…2 assume when the
network is idle and Parameter 53 is set to 0.
0 = OFF
1 = ON

Parameter Number

54

Access Rule

GET/SET

Data Type

BOOL

Group

Drive DeviceNet

Units

Minimum Value

0

Maximum Value

1

Default Value

0