Bulletin 284 Programmable Parameters for Sensorless Vector Controllers

Table 6.3

155 (Relay Out Sel)
Sets the condition that changes the state of the output relay contacts.

Parameter Number

155

Related Parameters

133, 156, 192, 240…247,

250…257, 260, 261

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

Minimum Value

0

Maximum Value

22

Default Value

22

Options

Description

0

Ready/Fault

(Default)

Relay changes state when power is applied. This indicates the drive is ready for operation. Relay returns drive to
shelf state when power is removed or a fault occurs.

1

At Frequency

Drive reached commanded frequency.

2

MotorRunning

Motor is receiving power from drive.

3

Reverse

Drive is commanded to run in reverse direction.

4

Motor Overld

Motor overload condition exists.

5

Ramp Reg

Ramp regulator is modifying the programmed accel/decal times to avoid overcurrent or overvoltage fault from
occurring.

6

Above Freq

Drive exceeds the frequency (Hz) value set in Parameter 156 (Relay Out Level) Use Parameter 156 to set
threshold.

7

Above Cur

Drive exceeds the current (% Amps) value set in Parameter 156 (Relay Out Level) Use Parameter 156 to set
threshold.

8

Above DCVolt

Drive exceeds the DC bus voltage value set in Parameter 156 (Relay Out Level). Use Parameter 156 to set
threshold.

9

Retries Exst

Value set in Parameter 192 (Auto Rstrt Tries) is exceeded.

10

Above Anlg V

Option not valid for Bulletin 284 ArmorStart.

11

Logic In 1

An input is programmed as Logic In 1 and is active.

12

Logic In 2

An input is programmed as Logic In 2 and is active.

13

Logic In 1 & 2

Both Logic inputs are programmed and active.

14

Logic In 1 or 2

One or both Logic inputs are programmed and one or both is active.

15

StpLogic Out

Drive enters Step Logic step with Digit 3 of Command Word (Parameters 240…247).

16

Timer Out

Timer has reached value set in Parameter 156 (Relay Out Level). Use Parameter 156 to set threshold.

17

Counter Out

Counter has reached value set in Parameter 156 (Relay Out Level). Use Parameter 156 to set threshold.

18

Above PF Ang

Power factor angle has exceeded the value set in Parameter 156 (Relay Out Level). Use Parameter 156 to set
threshold.

19

Anlg In Loss

Analog input loss has occurred. Program parameter 122 (Analog In Los) for desired action when loss occurs

20

ParamControl

Enables the output to be controlled over the network communications by writing to Parameter 156 (Relay Out
Level) (0 = Off, 1 = ON).

21

NonRec Fault

Value set in Parameter 192 (Auto Rstrt Tries) is exceeded.

22

EM Brk Cntrl

EM Brake is energized. Program Parameter 260 (EM Brk Off Delay) and Parameter 262 (EM Brk On Delay) for
desired action.