Devicenet group – Rockwell Automation 284 ArmorStart User Manual User Manual

Page 99

Advertising
background image

Bulletin 283 Programmable Parameters

4-9

DeviceNet Group

Autobaud Enable

When this parameter is enabled,
the device will attempt to
determine the network baud rate
and set its baud rate to the same,
provided network traffic exists.
At least one node with an
established baud rate must exist
on the network for autobaud to
occur.
0 = Disable
1 = Enable

Parameter Number

10

Access Rule

GET/SET

Data Type

BOOL

Group

DeviceNet

Units

Minimum Value

0

Maximum Value

1

Default Value

1

Consumed I/O Assy

This parameter selects the
format of the I/O data consumed.
Enter a Consumed I/O assembly
instance number to select a data
format.

Parameter Number

11

Access Rule

GET/SET

Data Type

USINT

Group

DeviceNet

Units

Minimum Value

0

Maximum Value

187

Default Value

160

Produced I/O Assy

This parameter selects the
format of the I/O data produced.
Enter a Produces I/O assembly
instance number to select a data
format.

Parameter Number

12

Access Rule

GET/SET

Data Type

USINT

Group

DeviceNet

Units

Minimum Value

0

Maximum Value

190

Default Value

161

Prod Assy Word 0

This parameter is used to build
bytes 0-1 for produced assembly
120

Parameter Number

13

Access Rule

GET/SET

Data Type

USINT

Group

DeviceNet

Units

Minimum Value

0

Maximum Value

116

Default Value

1

Advertising
This manual is related to the following products: