Product Overview

1-3

Current Limit Start

This starting mode is used when it is necessary to limit the maximum
starting current. It can be adjusted for 150...600% of full load amps.
Start times are selectable from 1...45 seconds.

Selectable Kick Start

A kickstart, or boost, at the beginning of the start mode is intended to
provide a current pulse of 450% of full load current. The kickstart
time is adjustable from 0.5...1.5 seconds. This allows the motor to
develop additional torque at start for loads which may need a boost to
get started.

Soft Stop

The Soft Stop function can be used with applications that require an
extended coast to rest. When enabled, the voltage ramp down time
can be selected from 1...90 seconds. The motor will stop when the
motor voltage drops to a point where the load torque is greater than
the motor torque.