Bulletin 284 Programmable Parameters for Volts per Hertz Controllers

5-35

Basic Program Group

Motor NP Volts
Set to the motor nameplate rated volts.

Parameter Number

131

Related Parameters

104, 184

Access Rule

GET/SET

Data Type

UINT

Group

Basic Program Setup

Units

1V AC

Minimum Value

20

Maximum Value

240V, 460V, or 600V AC

Default Value

Based on Drive Rating

Motor NP Hertz
Set to the motor nameplate rated frequency.

Parameter Number

132

Related Parameters

184, 190

Access Rule

GET/SET

Data Type

UINT

Group

Basic Program Setup

Units

1 Hz

Minimum Value

10

Maximum Value

240

Default Value

60 Hz

Motor OL Current
Set to the maximum allowable current. The drive will fault on an F7 Motor Over load
if the value of this parameter is exceeded by 150% for 60 seconds.

Parameter Number

133

Related Parameters

155, 189, 190, 198, 214

Access Rule

GET/SET

Data Type

UINT

Group

Basic Program Setup

Units

0.1 A

Minimum Value

0.0

Maximum Value

Drive rated amps x 2

Default Value

Based on Drive Rating

Minimum Freq
Sets the lowest frequency the drive will output continuously.

Parameter Number

134

Related Parameters

101, 102, 113, 135, 210, 212,

215

Access Rule

GET/SET

Data Type

UINT

Group

Basic Program Setup

Units

0.1 Hz

Minimum Value

0.0

Maximum Value

240

Default Value

0.0

Stop drive before changing this parameter.

Stop drive before changing this parameter.