Armorconnect™ three-phase power media, Trunk cables, Specifications dimensions – Rockwell Automation 284 ArmorStart User Manual User Manual

Page 334

Advertising
background image

A-14

Specifications

ArmorConnect™ Three-Phase
Power Media

Trunk Cables

Specifications

Dimensions

Dimensions are approximate. Illustrations are not drawn to scale.

Certifications

Standards Compliance

UL 2237

Mechanical

Coupling Nut

Black Anodized Aluminum or 316 Stainless Steel

Housing

Black PVC

Insert

Black PVC

Cable Diameter

0.775 in. +/- 0.12 in. (19.68 mm +/- 0.5 mm)

Electrical

Contacts

Copper Alloy with Gold over Nickel Plating

Cable

Black PVC, dual rated UL TC/Open Wiring and STOOW

Cable Rating

600V AC/DC

Assembly Rating

600V @ 25 A, Symmetrical Amps RMS Fault: 65 kA when

used with Class CC, T, or J type fuses

Environmental

Enclosure Type Rating

IP67, NEMA 4; IP69K 1200 psi washdown

Operating Temperature

UL Type TC 600V 90 °C Dry 75 °C Wet, Exposed Run (ER) or

MTW 600V 90 °C or STOOW 105 °C 600V -

CSA STOOW 600V FT2

88.9 (3.50)

38.6

(1.52)

Female straight

(1.95 - 2.25)

(2.94)

(1.52)

74.7

49.5 - 57.1

38.6

Female 90 deg.

88.9 (3.50)

38.6
(1.52)

Male straight

(1.95 - 2.25)

(2.94)

(1.52)

74.7

49.5 - 57.1

38.6

Male 90 deg.

Advertising