Rockwell Automation 284 ArmorStart User Manual User Manual

Page 430

Advertising
background image

D-30

Bulletin 284 CIP Information

Control Supervisor Object — CLASS CODE 0x0029

No class attributes will be supported. A single instance (instance 1) of
the Control Supervisor Object will be supported

Table D.58 Instance 1 — Control Supervisor Object.

Attribute ID

Access Rule

Name

Data Type

Value

3

Get/Set

Run FWD

BOOL

These Run outputs also map to
DOP instances 1 and 2.

4

Get/Set

Run REV

BOOL

7

Get

Running FWD

BOOL

8

Get

Running REV

BOOL

9

Get

Ready

BOOL

10

Get

Tripped

BOOL

12

Get/Set

Fault Reset

BOOL

0->1 = Trip Reset

100

Get/Set

Keypad Mode

BOOL

0=Maintained; 1=Momentary

101

Get/Set

Keypad Disable

BOOL

0=Not Disabled; 1=Disabled

115

Get

Warning Status

WORD

Bits 0-1 = reserved
Bit 2 = reserved
Bit 3 = reserved
Bit 4 = reserved
Bit 5 = CP Warning
Bit 6 = IO Warning
Bit 7 = reserved
Bit 8 = reserved
Bit 9 = DN Warning
Bits 10-12 = reserved
Bit 13 = HW Warning
Bits 14-15 = reserved

124

Get/Set

Trip Enable

WORD

Bit enumerated trip enable word

130

Get/Set

Trip Reset Mode

BOOL

0=manual; 1=auto

131

Get/Set

Trip Reset Level

USINT

0 – 100%; default = 75

150

Get/Set

High Speed Ena

BOOL

0 = Disable; 1 = Enable

151

Get

Base Enclosure

WORD

Bit 0 = IP67
Bit 1 = NEMA 4x
Bits 2-15 reserved

152

Get

Base Options

WORD

Bit 0 = Output Fuse
Bit 1 = Safety Monitor
Bit 2 = CP Fuse Detect
Bits 3-7 = Reserved
Bit 8 = 10A Base
Bit 9 = 25A Base
Bit 10-15 = Reserved

153

Get

Wiring Options

WORD

Bit 0 = Conduit
Bit 1 = Round Media
Bits 2-15 = Reserved

154

Get

Starter Enclosure

WORD

Bit 0 = IP67
Bit 1 = NEMA 4x
Bits 2-15 reserved

156

Get

Last PR Trip

UINT