Rockwell Automation 284 ArmorStart User Manual User Manual

Page 120

Advertising
background image

4-30

Bulletin 283 Programmable Parameters

Table 4.2

FLA Setting Ranges and Default Values (with indicated setting

precision)

Recommended maximum start time is 15 seconds.

Recommended maximum current limit setting is 350%.

FLA Current Range (A)

Default Value

Minimum Value

Maximum Value

1.1

3.0

1.1

3.0

5.5

3.0

5.3

7.6

5.3

6.3

16.0

6.3

OL Reset Level

This parameter allows the
installer select the % Thermal
Capacity which an overload can
be cleared

Parameter Number

108

Access Rule

GET/SET

Data Type

USINT

Group

Soft Start Setup

Units

% FLA

Minimum Value

0

Maximum Value

100

Default Value

75

Start Time

This parameter allows the
installer to select the start time of
1…45 seconds

Parameter Number

109

Access Rule

GET/SET

Data Type

USINT

Group

Soft Start Setup

Units

Sec

Minimum Value

1

Maximum Value

45

Default Value

10

Start Mode

This parameter allows the
installer to select either soft stop
or current limit

1= Current Limit
0= Soft Start

Parameter Number

110

Access Rule

GET/SET

Data Type

BOOL

Group

Soft Start Setup

Units

Minimum Value

0

Maximum Value

1

Default Value

0

Current Limit

This parameter allows the
installer to select the value of the
current limit setting of
150…600% of the full load amps

Parameter Number

111

Access Rule

GET/SET

Data Type

UINT

Group

Soft Start Setup

Units

% of Motor FLA

Minimum Value

150

Maximum Value

600

Default Value

350

Advertising