Bulletin 283, continued, A-6 specifications – Rockwell Automation 284 ArmorStart User Manual User Manual

Page 326

Advertising
background image

A-6

Specifications

Bulletin 283, Continued

Electrical Ratings

UL/NEMA

IEC

Environmental

Operating Temperature Range

–20…40°C (–4…104°F)

Storage and Transportation

temperature range

–25….85°C (–13…185°F)

Altitude

2000 m

Humidity

5…95% (non-condensing)

Pollution Degree

3

Mechanical Resistance to Shock

Operational 15

G

Non-Operational 30

G

Resistance to Vibration

Operational

1 G, 0.15 mm (0.006 in.) displacement

Non-Operational 2.5

G,

0.38 mm (0.015 in.) displacement

Control Power and Safety Monitor

Terminal Cable Size

Primary/ Secondary Terminal:

#18…#10 AWG

Primary/ Secondary Terminal:

1.0 …4.0 mm

2

Tightening Torque

6.2 in·lb

0.7 N·m

Line Power Terminal cable size

#16…#10 AWG

1.5…4.0 mm

2

Tightening Torque

4.5 in·lb

0.5 N·m

Ground Terminal cable size

#18…#10 AWG

1.0…4.0 mm

2

Tightening Torque

4.5 in·lb

0.5 N·m

Enclosure Ratings

NEMA Type 4/12/13 or NEMA Type 4X

IP67 or IP69K

Approximate Shipping Weight

16.8 kg (37 lbs.)

Other Rating

EMC Emission levels

Conducted Radio Frequency Emissions

Class A

Radiated Emissions

Class A

EMC immunity levels

Electrostatic Discharge

4 kV contact and 8 kV Air

Radio Frequency Electromagnetic Field

10 V/m

Fast Transient

2 kV

Surge Transient

1 kV L-L, 2 kV L-N (Earth)

Overload Characteristics

Overload Current Range

1.1…3.0 A

3.0…5.5 A

5.3…7.6 A

6.3…16 A

Trip Class

10

Trip Rating

120% of FLC setting

Number of poles

3

DeviceNet Specifications

DeviceNet Supply Voltage Rating

Range 11…25V DC, 24V DC Nominal

DeviceNet Input Current

167 mA @ 24V DC - 4.0 W

364 mA @ 11V DC - 4.0 W

External Devices powered by DeviceNet

Sensors Inputs 4 * 50 mA - total 200 mA

Total w/max. Sensor Inputs (4)

367 mA @ 24V DC - 8.8 W

DeviceNet Input Current Surge

15 A for 250 µs

DeviceNet Communications

Baud Rates

125, 250, 500 kbps

Distance Maximum

500 m (1630 ft) @ 125 kbps

200 m (656 ft) @ 250 kbps

100 m (328 ft) @ 500 kbps

Certifications

cULus (File No. E96956)

UL 508

EN/IEC 60947-4-2

CE Marked per Low Voltage Directive 73/23/EEC and EMC Directive 89/336/EEC

Advertising