Rockwell Automation 284 ArmorStart User Manual User Manual

Page 198

Advertising
background image

6-24

Bulletin 284 Programmable Parameters for Sensorless Vector Controllers

Control Source
Displays the source of the Start Command and Speed Reference.
Valid Start Commands for the Bulletin 284 ArmorStart are the following:
2 = 2-wire
3 = 2-wire Level Sensitive
4 = 2-wire High Speed
5 = RS485 (DSI) Port
9 = Jog
Valid Speed Commands for the Bulletin 284 ArmorStart are the following:
1 = Internal Frequency
2 = 0…10V Input/Remote Potentiometer
4 = Preset Freq X
5 = RS485 (DSI) port
6 = Step Logic Control
9 = Jog Freq

Parameter Number

112

Related Parameters

136, 138, 151…154 (Digital

Inx Sel) must be set to 4, 169,

170…177 (Preset Freq X),

240…247 (Step Logic

Control)

Access Rule

GET

Data Type

UINT

Group

Display Group

Units

1

Minimum Value

0

Maximum Value

9

Default Value

5

Contrl In Status
Status of the control terminal block control inputs:
Bit 0 = Start/Run FWD input
Bit 1 = Direction/Run REV Input
Bit 2 = Stop Input
Bit 3 = Dynamic Brake Transistor On

Parameter Number

113

Related Parameter

102, 134, 135

Access Rule

GET

Data Type

UINT

Group

Display Group

Units

1

Minimum Value

0

Maximum Value

1

Default Value

0

Dig In Status
Status of the control terminal block digital inputs:
Bit 0 = Digital IN 1 Sel
Bit 1 = Digital IN 2 Sel
Bit 2 = Digital IN 3 Sel
Bit 3 = Digital IN 4 Sel

Parameter Number

114

Related Parameter

151…154

Access Rule

GET

Data Type

UINT

Group

Display Group

Units

1

Minimum Value

0

Maximum Value

1

Default Value

0

Comm Status
Status of communications ports:
Bit 0 = Receiving Data
Bit 1 = Transmitting Data
Bit 2 = RS485
Bit 3 = Communication Error

Parameter Number

115

Related Parameter

203…207

Access Rule

GET

Data Type

UINT

Group

Display Group

Units

1

Minimum Value

0

Maximum Value

1

Default Value

0