Bulletin 283, Specifications a-5 – Rockwell Automation 284 ArmorStart User Manual User Manual

Page 325

Advertising
background image

Specifications

A-5

Bulletin 283

Electrical Ratings

UL/NEMA

IEC

Power Circuit

Rated Operation Voltage

200V…575V

200…600V

Rate Insulation Voltage

600V

500V

Rated Impulsed Voltage

6 kV

6 kV

Dielectric Withstand

2200V AC

2500V AC

Operating Frequency

50/60 Hz

50/60 Hz

Utilization Category

N/A

AC-3

Protection Against Shock

N/A

IP2X

Rated Operating Current Max.

3.0 A / 5.5 A / 7.6 A / 16 A

Short Circuit
Protection

SCPD performance Type 1

Current Rating

Voltage

480Y/277V

480/480V

600Y/347V

600V

1.1…3.0 A

Sym. Amps

RMS

65 kA

65 kA

30 kA

30 kA

3.0…5.5 A

5.3…7.6 A

6.3…16 A

30 kA

30 kA

30 kA

30 kA

SCPD List

Size per NEC Group Motor

Control Circuit

Rated Operation Voltage

24V DC (+10%, -15%) A2 (should be grounded at voltage source)

120V AC (+10%, -15%) A2 (should be grounded at voltage source)

240V AC (+10%, -15%) A2 (should be grounded at voltage source)

Rate Insulation Voltage

250V

250V

Rated Impulsed Voltage

4 kV

Dielectric Withstand

1500V AC

2000V AC

Overvoltage Category

III

Operating Frequency

50/60 Hz

50/60 Hz

Power Requirements

Units

Control Voltage (Nom)

Volts

24V DC

120V AC

240V AC

Power Supply (Nom)

Amps

0.170

0.110

0.060

Total Control Power (Starting/Stopping)

VA (W)

(90.0 W)

35

35

Total Control Power (Running)

VA (W)

(8.0 W)

28

28

External Devices powered by Control Voltage

Outputs (2) 1 A max. each)

Amps

2

2

2

Total Control (Starting/Stopping) with max. outputs

VA (W)

(138.0 W)

275

515

Total Control (Running) with max. outputs

VA (W)

(56.0 W)

268

508

Input Ratings

Rated Operation Voltage

24V DC

Input On-State Voltage Range

10…26V DC

Input On-state Current

3.0 mA @ 10V DC

7.2 mA @ 24V DC

Input Off-state Voltage Range

0…5V DC

Input Off-state Current

<1.5 mA

Input Filter — Software Selectable

Off to On

Settable from 0…64 ms in 1 ms increments

On to Off

Settable from 0…64 ms in 1 ms increments

Input Compatibility

N/A

IEC 1+

Number of inputs

4

Sensor Source

Voltage Status Only

11…25V DC from DeviceNet™

Current Available

50 mA MAX per Input, 200 mA Total

Output Ratings (Sourced
from Control Circuit)

Rated Operation Voltage

240V AC / 30V DC

240V AC / 30V DC

Rate Insulation Voltage

250V

250V

Dielectric Withstand

1500V AC

2000V AC

Operating Frequency

50/60 Hz

50/60 Hz

Type of control circuit

Electromechanical Relay

Kind of Current

AC/DC

Conventional Thermal Current I

th

Total of both outputs

2 A

Type of Contacts

Normally Open (N.O.)

Number of Contacts

2

ArmorPoint® Ratings

Backplane Current Load

400 mA

Advertising
This manual is related to the following products: