6-20

Bulletin 284 Programmable Parameters for Sensorless Vector Controllers

Drive DeviceNet Group

Drive Control
This parameter provides the status of drive parameters.

Parameter Number

48

Access Rule

GET

Data Type

WORD

Group

Drive DeviceNet

Units

Minimum Value

0

Maximum Value

4095

Default Value

0

Bit

Function

11

10

9

8

7

6

5

4

3

2

1

0

X

Accel 1 En

X

Accel 2 En

X

Decel 1 En

X

Decel 3 En

X

Freq Sel 0

X

Freq Sel 1

X

Freq Sel 2

X

Reserved

X

Drv In 1

X

Drv In 2

X

Drv In 3

X

Drv In 4

Drvin PrFltState
This parameter, in conjunction with Parameter 50, defines how the Drive Digital
Inputs 1…4 will respond when a protection trip occurs. When set to 1, Drive Digital
Inputs 1…4 continue to operate as command via the network. When set to 0, Drive
Digital Inputs 1…4 will open or close as determined by setting in Parameter 50.
0 = Go to PrFlt Value
1 = Ignore PrFlt

Parameter Number

49

Access Rule

GET/SET

Data Type

BOOL

Group

Drive DeviceNet

Units

Minimum Value

0

Maximum Value

1

Default Value

0

Drvin PrFltValue
This parameter determines the state of Drive Digital Inputs 1…4, assumes when a
trip occurs and Parameter 49 is set to 0.
0 = Open
1 = Close

Parameter Number

50

Access Rule

GET/SET

Data Type

BOOL

Group

Drive DeviceNet

Units

Minimum Value

0

Maximum Value

1

Default Value

0