Bulletin 284 Programmable Parameters for Sensorless Vector Controllers

6-49

Figure 6.6

Anlg In 0…10V Lo

Sets the analog input level that corresponds to parameter 134 (Minimum Freq) if a
0…10V input is used by parameter 138 (Speed Reference)

Parameter Number

210

Related Parameter

121, 134, 138, 222

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

0.1%

Minimum Value

0.0%

Maximum Value

100.0%

Default Value

0.0%

Stop drive before changing this parameter.

Anlg In 0…10V HI

Sets the analog input level that corresponds to parameter 135 (Maximum Freq) if a
0…10V input is used by parameter 138 (Speed Reference). Analog inversion can be
accomplished by setting this value smaller than parameter 210 (Anlg In 0…10V Lo).

Parameter Number

211

Related Parameter

121, 135, 138, 222, 223

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

0.1%

Minimum Value

0.0%

Maximum Value

100.0%

Default Value

0.0%

Anlg In4…20MA LO
This parameter is not available for use with the ArmorStart Distributed Motor
Controller.

Parameter Number

212

Anlg In4…20 mA HI
This parameter is not available for use with the ArmorStart Distributed Motor
Controller.

Parameter Number

213

0

Parameter 135

[Maximum Freq]

Parameter 134

[Minimum Freq]

Parameter 210

[Anlg In 0-10V Lo]

Parameter 211

[Anlg In 0-10V Hi]

0

Speed Reference

Stop drive before changing this parameter.