Bulletin 284 Programmable Parameters for Volts per Hertz Controllers

5-47

Clear an Overvoltage, Undervoltage, or Heatsink OvrTmp Fault
without Restarting the Drive

1. Set Parameter 192 (Auto Rstrt Tries) to a value other than 0.

2. Set Parameter 193 (AutoRstrt Delay) to 0.

ATTENTION

!

Equipment damage and/or personal injury may result if this parameter is used
in an inappropriate application. Do not use this function without considering
applicable local, national, and international codes, standards, regulations, or
industry guidelines.

Auto Rstrt Delay
Sets time between restart attempts when Parameter 192 (Auto Rstrt Tries) is set to a
value other than zero.

Parameter Number

193

Related Parameters

192

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

0.1 sec

Minimum Value

0.0

Maximum Value

300.0 sec

Default Value

1.0 sec

Start at PowerUp

Enables/disables a feature that allows a Start or Run command to automatically
cause the drive to resume running at command speed after the drive input is
restored. Requires a digital input configured Run or Start and a valid start contact.
This parameter will not function if Parameter 136 (Start Source) is set to 4 2-W High
Speed
.
0 = Disabled
1 = Enabled

Parameter Number

194

Related Parameters

192

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

Minimum Value

0

Maximum Value

1

Default Value

0

Stop drive before changing this parameter.

ATTENTION

!

Equipment damage and/or personal injury may result if this
parameter is used in an inappropriate application. Do not use
this function without considering applicable local, national, and
international codes, standards, regulations, or industry
guidelines.