background image

14-18

Troubleshooting

Base Module Replacement
(Bulletin 280/281)

Removal of Base Module

1) Disconnect from power source.

2) Remove motor cable, comunication cables and all others connected
to the inputs and outputs.

3) Loosen four mounting screws on the Starter Module.

4) Unplug the Control Module from the base by pulling forward.

5) Loosen four mounting screws on the Terminal Access Cover Plate.

6) Remove cover plate.

7) Loosen terminal screws.

8) Remove all wires from terminal block.

Figure 14.4 Bulletin 280/281 Base Module Removal

ATTENTION

!

To avoid shock hazard, disconnect main power
before working on the controller, motor, or control
devices

Note: DeviceNet base module is

shown

1

2

5

6

4

2

8

7

3

Base Module

Input/Output Cable

Communication
Cable

Motor Cable

Control Module

Terminal Access
Cover Plate