5-44

Bulletin 284 Programmable Parameters for Volts per Hertz Controllers

Figure 5.2

Boost Select
Sets the boost voltage (% of Parameter 131 [Motor NP Volts]) and redefines the Volts
per Hz curve. Active when Parameter 225 (Torque Perf Mode) = 0V/Hz Drive may
add additional voltage unless Option 5 is selected.

See Table 5.E for details

Parameter Number

184

Related Parameters

104, 131, 132

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

Minimum Value

1

Maximum Value

14

Default Value

8

Table 5.E Boost Select Options

Options

Description

1

30.0, VT

Variable Torque (Typical fan/pump

curves)

2

35.0, VT

3

40.0, VT

4

45.0, VT

5

0.0 no IR

Constant Torque

6

0.0

7

2.5, CT (Default for 5 Hp/3.7 kW Drive)

8

5.0, CT Default

9

7.5,CT

10

10.0,CT

11

12.5,CT

12

15.0,CT

13

17.5,CT

14

20.0,CT

% Parameter 132 (Motor NP Hertz)

% Parameter 131 (Motor NP V

olts)

1/2 (Motor NP Volts)

Settings

5...14

0

50

100

50

100

4

1

2

3

1/2

(Motor NP Hertz)