13-2

Diagnostics

Clear Fault

You may clear a fault using the following methods:

Remotely via network communications

A remote reset will be attempted upon detection of a rising edge
(0 to 1 transition) of the “Fault Reset” bit in the various I/O
assemblies. A remote reset will also be attempted upon detection
of the rising edge of the “Fault Reset” parameter.

Locally via the “Reset” button on the LED Status indication
keypad.

Fault Codes

Table 13.1 provides a complete reference of the Fault LED
indications for Bulletin 280 and 281 ArmorStart Distributed Motor
Controllers.

Table 13.1 Fault Indication

Not available on the Bulletin 280A/281A., 283A, or 284A

Blink

Pattern

Fault Types

Bulletin 280/281

Bulletin 283

Bulletin 284

1

Short Circuit

Short Circuit

Short Circuit

2

Overload Trip

Overload Trip

Overload Trip

3

Phase Loss

Phase Loss

Phase Short

4

Reserved

Shorted SCR

Ground Fault

5

Reserved

Phase Rotation

Stall

6

Control Power

Control Power

Control Power

7

I/O Fault

I/O Fault

I/O Fault

8

Over Temperature

Over Temperature

Over Temperature

9

Phase Imbalance

Phase Imbalance

Over Current

10

DeviceNet™ Power

Loss

DeviceNet™ Power

Loss

DeviceNet™ Power

Loss

11

Reserved

Internal

Communications

Internal

Communications

12

Reserved

Heatsink Over

Temperature

DC Bus Fault

13

EEPROM Fault

EEPROM Fault

EEPROM Fault

14

Hardware Fault

Hardware Fault

Hardware Fault

15

Reserved

Reserved

Restart Retries

16

Reserved

Misc. Fault

Misc. Fault