Bulletin 280/281 Programmable Parameters

3-7

DeviceNet Group

Comm Override

This parameter allows for local
logic to override the absence of
an I/O connection
0 = Disable
1 = Enable

Parameter Number

9

Access Rule

GET/SET

Data Type

BOOL

Group

DeviceLogix

Units

Minimum Value

0

Maximum Value

1

Default Value

0

Autobaud Enable

When this parameter is enabled,
the device will attempt to
determine the network baud rate
and set its baud rate to the same,
provided network traffic exists.
At least one node with an
established baud rate must exist
on the network for autobaud to
occur.
0 = Disable
1 = Enable

Parameter Number

10

Access Rule

GET/SET

Data Type

BOOL

Group

DeviceNet

Units

Minimum Value

0

Maximum Value

1

Default Value

1

Consumed I/O Assy

This parameter selects the
format of the I/O data consumed.
Enter a Consumed I/O assembly
instance number to select a data
format.

Parameter Number

11

Access Rule

GET/SET

Data Type

USINT

Group

DeviceNet

Units

Minimum Value

0

Maximum Value

187

Default Value

160

Produced I/O Assy

This parameter selects the
format of the I/O data produced.
Enter a Produces I/O assembly
instance number to select a data
format.

Parameter Number

12

Access Rule

GET/SET

Data Type

USINT

Group

DeviceNet

Units

Minimum Value

0

Maximum Value

190

Default Value

161